Hold-downs
Hold-down embedment per design specs . . . . . . . .[manu.] {manu.}
Bolts installed to manufacturer's specs . . . . . . . .[manu.] {manu.}
All load transfers floor to floor to design specs . . .[601.2] {1629}
Concrete Masonry Units (CMUs)
General Requirements 6in. block OK for one story to 9ft. . . . . . . . . . . .[606.2.1] {2109.6.1}
8in. block if more than one story or >9ft. . . . . . .[606.2.1] {2109.6.1}
Beam connections--2in. airspace on three sides [323.1] {2306.6}
Roof & floor structures to be anchored
to masonry walls . . . . . . . . . . . . . . . . . . . .F-b5 [606.10] {2309}
Grout
All cells with reinforcement must be filled . . . . . .[609.4.1] {2104.6.1}
Cleanouts req'd at bottom of each
grouted cell for pours >4ft. {5ft.} . . . . . . . . . .[609.1.5.2] (2104.6.1}
Grout continuous pour max. lift 5ft. . . . . . . . . . .[609.1.4] {2104.6.1}
Clean grout space--max. 2in. projections . . . . .[609.1.3] {2104.6.1}
Reinforcing
SDC D1&D2: min. #3 vertical bars 4ft. o.c. . . . .[404.1.4] {2106.1.12.4}
Vertical Rebar <=6% of grout space . . . . . . . . . .[T609.1.2] {2107.2.2.1}
Lap Rebar splices 40x bar dia. . . . . . . . . . . .[F606.10(2)] {2107.2.2.6}
Support/positioners min. 200 bar dia. (8ft. #4 bar) [609.4.1] {2104.5}
Cover--min. win.; 2in. to weather or soil . . . . . . [606.12] {2107.2.2.2}
Retaining Walls
Walls supporting >4ft. of backfill req. design . . .[404.1.3] {106.2}
Surcharge within >45° must be engineered [105.2,404.1.3] {1804.6}
Enclosing habitable space--req's. moisture barrier [406.1] {1833.1}
Books based on 2006 IRC, UMC, & UPC; 2005 & 2008 NEC; 2007 CBC, CPC, CMC & CEC with references to changes from prior editions. Books are published by The Taunton Press Inc. Code Check Copyright 2009 • Code Check is a registered trademark of the Taunton Press, Inc., registered in the U.S. Patent & Trademark Office