Fireblocking In concealed spaces every 10ft. horiz. and vert. . . . . . .[602.8] {708.2.1}
Horiz./vert. intersections
such as soffits, drop & cove ceilings . . . . . . . . . . . . . . .[602.8] {708.2.1}
Concealed space under stairs at top and bottom of stringers . .[602.8] {708.2.1}
Gaps around ducts and pipes must be sealed w/approved material @ floor & ceiling level penetration . . . . . . . . . . . . . . . . . . . . . . . . . . . [602.8] {708.2.1}
Material may be 2x lumber, 2" gyp. board, compressed glass fiber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [602.8.1] {708.2.2}
Separation from Garage
Min. 2in. {5/8in.} gyp. board on
garage side of walls/ceilings common to house . . . . . . .[309.2] {302.4Exc.}
Min. 2in. gyp. board on walls supporting ceilings common to house
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [309.2] {302.2}
Exterior walls <3ft. from property line 1hr. construction [302.1]{T-5-A}
Ducts through wall or ceiling common to house min. 26 ga. steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [309.1.1] {302.4Exc.}
No duct openings in garage . . . . . . . . . . . . . . . . . . .[309.1.1] {302.4X}
Door to house rated 20-minute or 1sin. solid-core {self-closing}
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [309.1] {302.4X}
Non-combustible floor[with slope to vehicle door or to a drain]. . .[309.3] {312.5}
16sq.in. max. size for electrical boxes penetrating membrane
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [321.3.2X] {709.7X}
No back-to-back electrical boxes(24in. horiz. separation) . .[321.3.2X] {709.7X}
Listed plastic boxes or putty pads OK . . . . . . . . . . .[321.3.2X] {709.7X}
Electrical panel {not} OK in garage side of common wall . . [n/a] {709.7X}
Separation Walls in 2-Family Dwellings 1hr. construction req'd at common walls & floor/ceiling [321.1] {310.1}
Rating of 2hr. OK if automatic sprinkler system present [321.1X] {310.1}
Separation Walls in Multi-Family Dwellings 1hr. construction req'd at common walls & floor/ceiling . . .[n/a] {310.2.1}
All construction (exc. nonbearing interior partitions)
min. 1hr. if >2 stories or >3,000sq.ft. above first floor . . .[n/a] {310.2.2}
1 hr. construction between storage/laundry and dwellings [n/a] {310.2.2}
Common attic spaces sprinklered or
Chimneys Min. 4 #4 vertical reinforcing bars solidly grouted . . .[1003.3.1] {3102.4.3}
Min. 4in. horizontal ties each 18in. . . . . . . . . . . . .[1003.3.2] {3102.4.3}
Anchored at each floor or ceiling >6ft. above grade unless completely in
building interior. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .[1003.4] {3102.4.3}
Min. 2in. separation between chimney & combustibles [1001.15] {3102.7.8}
Min. 2ft. above any part of building within 10ft. and min. 3ft. where passing through roof. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [1001.6] {3102.3.6}
Spark arrester req'd . . . . . . . . . . . . . . . . . . . . . . . . . . .[local] {3102.3.8}
Spark arrester min. area 4x flue opening . . . . . . . . . . . .[local] {3102.3.8}
Spark arrester mesh sin. min. 2in. max. . . . . . . . . . . .[local] {3102.3.8}
Factory built chimney must be installed per listing . . .[1002.1] {3102.5.1}
Decorative chimney shrouds must be listed for fireplace system .
...................................................... . . . . . . . .[1002.2,1004.3] {3102.5.1}
Dry Walls
Gypsum Board Installed only after all rough inspections complete . . . . .[109.4] {108.5.4}
Installed after building is weathertight . . . . . . . . . . . . .[701.2] {1402.1}
Nailing per schedule . . . . . . . . . . . . . . . . . . .T-b10[T702.3.5] {2511.2}
Insulation
Vapor barrier facing conditioned space . . . . . . . . . . . .[1101.3] {707.3}
Tight around insulation-rated ceiling lights . . . . . . .[1102.1.10] {manu}
Installer to provide certificate for blown-in . . . . . . . .[1101.3.1] {local}
Sound & Fire Assemblies Assemblies are tested and recommended by the Gypsum Association. Adjoining
dwelling units should have a minimum sound rating of STC 50 (Sound Transmission
Class) and a 1hr. fire-resistance rating. These are only samples of the
numerous assemblies possible. See Gypsum Association manuals for more.
Books based on 2006 IRC, UMC, & UPC; 2005 & 2008 NEC; 2007 CBC, CPC, CMC & CEC with references to changes from prior editions. Books are published by The Taunton Press Inc. Code Check Copyright 2009 • Code Check is a registered trademark of the Taunton Press, Inc., registered in the U.S. Patent & Trademark Office