Code Check Training Centers
Building Code Reference!

Fire Protection

Fireblocking
In concealed spaces every 10ft. horiz. and vert. . . . . . .[602.8] {708.2.1}
Horiz./vert. intersections
such as soffits, drop & cove ceilings . . . . . . . . . . . . . . .[602.8] {708.2.1}
Concealed space under stairs at top and bottom of stringers . .[602.8] {708.2.1}
Gaps around ducts and pipes must be sealed w/approved material @ floor & ceiling level penetration . . . . . . . . . . . . . . . . . . . . . . . . . . . [602.8] {708.2.1}
Material may be 2x lumber, 2" gyp. board, compressed glass fiber
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [602.8.1] {708.2.2}

Separation from Garage
Min. 2in. {5/8in.} gyp. board on
garage side of walls/ceilings common to house . . . . . . .[309.2] {302.4Exc.}
Min. 2in. gyp. board on walls supporting ceilings common to house
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [309.2] {302.2}
Exterior walls <3ft. from property line 1hr. construction [302.1]{T-5-A}
Ducts through wall or ceiling common to house min. 26 ga. steel
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [309.1.1] {302.4Exc.}
No duct openings in garage . . . . . . . . . . . . . . . . . . .[309.1.1] {302.4X}
Door to house rated 20-minute or 1sin. solid-core {self-closing}
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [309.1] {302.4X}
Non-combustible floor[with slope to vehicle door or to a drain]. . .[309.3] {312.5}
16sq.in. max. size for electrical boxes penetrating membrane
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [321.3.2X] {709.7X}
No back-to-back electrical boxes(24in. horiz. separation) . .[321.3.2X] {709.7X}
Listed plastic boxes or putty pads OK . . . . . . . . . . .[321.3.2X] {709.7X}
Electrical panel {not} OK in garage side of common wall . . [n/a] {709.7X}

Separation Walls in 2-Family Dwellings
1hr. construction req'd at common walls & floor/ceiling [321.1] {310.1}
Rating of 2hr. OK if automatic sprinkler system present [321.1X] {310.1}

Separation Walls in Multi-Family Dwellings
1hr. construction req'd at common walls & floor/ceiling . . .[n/a] {310.2.1}
All construction (exc. nonbearing interior partitions)
min. 1hr. if >2 stories or >3,000sq.ft. above first floor . . .[n/a] {310.2.2}
1 hr. construction between storage/laundry and dwellings [n/a] {310.2.2}
Common attic spaces sprinklered or

Building Code Reference!

Exterior Wall Covers

General
Ext. wall shall prevent water penetration . . . . . . . . . . .[703.1] {1402.1}
All penetrations flashed watertight . . . . . . . . . . . . . . . .[703.8] {1402.2}

Stucco over Wire Fabric
PAPER:
Paper lap--horiz. 2in.; vert. 6in. . . . . . . . . . . . . . . . . .[703.2] {1402.1}
Min. 15# felt paper over wood studs or sheathing . . . . .[703.2] {2506.4}
All fasteners to be corrosion resistant . . . . . . . . . . . . .[703.4] {2506.2}
EIFS req. weather barrier . . . . . . . . . . . . . . . . . . . . .[703.9.1] {1402.1}

WIRE:
Wire lap min. one mesh or 1in. . . . . . . . . . . . . . . . . . . .[trade] {manu.}
Nail or staple spacing max. 6in. . . . . . . . . . . . . . . . .[703.6.1] {manu.}
Over solid sheathing no fasteners in field (not random) [manu.] {2506.3}
Lap paper/paper & wire/wire (not wire/paper/wire/paper) [703.1] {2506.3}
No holes on the top of horiz. surfaces (copings, etc.) . . .[703.1] {2506.4}
Weep screed 4in. to earth, 2in. to paved areas . . . . .[703.6.2] {2506.5}

Stucco Repairs
No paper/wire paper/wire laps . . . . . . . . . . . . . . . . . .[703.2] {manu.}
Expose 2in.-4in. of old paper; lap new under old except at top
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [703.2] {manu.}

Exterior Insulation Finish Systems (EIFS)
Must follow manu. instructions . . . . . . . . . . . . . . . . . .[703.9] {2508.1}
No decorative trim face nailed through EIFS . . . . . . . . .[703.9] {manu}
Special inspections req'd unless over masonry or weather barrier
...........................................................................T-b11 [703.9.1] {1701.1}

Building Code Reference!

Shower/Wet Walls

Greenboard (Water-Resistant Gypboard)
Not over vapor retarder . . . . . . . . . . . . . . . . . . . . . . . . .[local] {2512}
OK for adhesive ceramic tile . . . . . . . . . . . . . . . . . .[702.4.2l] {2512}
All edges must be sealed with water-resistant sealant [702.4.2]{manu.}
Not on ceilings with >12in. o.c. framing . . . . . . . . . . .[702.4.2] {2512}
Finish to extend min. 72in. {70} above drain . . . . . . . . .[307.2] {807.1.3}

Cement Board
Suitable for adhesive ceramic tile . . . . . . . . . . . . . . . . .[local] {local}
Req's building paper backing . . . . . . . . . . . . . . . . . . . .[manu.] {807.1.3}
Corrosion-resistant fasteners . . . . . . . . . . . . . . . . . . .[manu.] {807.1.3}
All joints covered with water resistant sealant . . . . . . .[702.4.2] {807.1.3}
Finish to extend min. 72in. {70} above drain . . . . . . . . .[307.2] {807.1.3}

Building Code Reference!

Fireplace

Fireplaces
Hearth slab min. thickness 4in. . . . . . . . . . . . . . . .[1003.9.1] {3102.7.11}
Hearth exten. distinguishable from surrounding floor . .[1004.2] {3102.7.12}
Hearth exten. depth 16in.front 8in. side if opening <6sq.ft.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-b19 [1003.10] {3102.7.12}
Hearth exten. depth 20in. front 12in. side if opening =>6sq.ft.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F-b19 [1003.10] {3102.7.12}
Manufactured fireplace must be installed per listing . . .[1004.1] {3102.5.1}
Glass doors req'd . . . . . . . . . . . . . . . . . . . . . . . .[1102.1.10] {energy}
All combustion air from outside . . . . . . . . . . . . . . . . .[1005.1] {energy}
No combustible material within 6in. of opening . . . . .[1003.13] {3102.7.8}
Combustible material <12in. of opening max. 8in. projection for each inch of clearance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-b20 [1003.13] {3102.7.8}

Chimneys
Min. 4 #4 vertical reinforcing bars solidly grouted . . .[1003.3.1] {3102.4.3}
Min. 4in. horizontal ties each 18in. . . . . . . . . . . . .[1003.3.2] {3102.4.3}
Anchored at each floor or ceiling >6ft. above grade unless completely in
building interior. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .[1003.4] {3102.4.3}
Min. 2in. separation between chimney & combustibles [1001.15] {3102.7.8}
Min. 2ft. above any part of building within 10ft. and min. 3ft. where passing through roof. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [1001.6] {3102.3.6}
Spark arrester req'd . . . . . . . . . . . . . . . . . . . . . . . . . . .[local] {3102.3.8}
Spark arrester min. area 4x flue opening . . . . . . . . . . . .[local] {3102.3.8}
Spark arrester mesh sin. min. 2in. max. . . . . . . . . . . .[local] {3102.3.8}
Factory built chimney must be installed per listing . . .[1002.1] {3102.5.1}
Decorative chimney shrouds must be listed for fireplace system .
...................................................... . . . . . . . .[1002.2,1004.3] {3102.5.1}





Building Code Reference!

Dry Walls


Gypsum Board
Installed only after all rough inspections complete . . . . .[109.4] {108.5.4}
Installed after building is weathertight . . . . . . . . . . . . .[701.2] {1402.1}
Nailing per schedule . . . . . . . . . . . . . . . . . . .T-b10 [T702.3.5] {2511.2}

Building Code Reference!

Insulation


Vapor barrier facing conditioned space . . . . . . . . . . . .[1101.3] {707.3}
Tight around insulation-rated ceiling lights . . . . . . .[1102.1.10] {manu}
Installer to provide certificate for blown-in . . . . . . . .[1101.3.1] {local}

Sound & Fire Assemblies
Assemblies are tested and recommended by the Gypsum Association. Adjoining
dwelling units should have a minimum sound rating of STC 50 (Sound Transmission
Class) and a 1hr. fire-resistance rating. These are only samples of the
numerous assemblies possible. See Gypsum Association manuals for more.






Google
Search codecheck.comSearch WWW


Books based on 2006 IRC, UMC, & UPC; 2005 & 2008 NEC; 2007 CBC, CPC, CMC & CEC with references to changes from prior editions. Books are published by The Taunton Press Inc.
Code Check Copyright 2009Code Check is a registered trademark of the Taunton Press, Inc., registered in the U.S. Patent & Trademark Office