General Gas test--3psi. {10psi-6in. mercury} for 10 {15} minutes [2416.4] {1204.3.2}
Gas meter--access opening min. 22in. x 24in. . . . . . . . . . [n/a] {1209.5}
Main shutoff ahead of meter, outside & readily accessible .[2419.2] {1209.3}
Material--wrought iron, steel (galv. or black) yellow brass [2413.1.] {1210.1}
Labeled "Gas for other than black pipe {Cu only} . . . . .[2411.5] {1211.8}
Copper OK for low sulfur-content gas . . . . . . . . . . . .[2413.5.2] {Ø}
Corrugated stainless-steel tubing permitted . . . . . . .[2413.5.3] {pending}
Interior of pipe must be deburred . . . . . . . . . . . . . . . . .[2413.7] {1210.2}
Plastic pipe only at exterior buried . . . . . . . . . . . . . . . .[2413.6] {1210.1}\
No gas pipe in circulating or ventilating air duct . . . . . . .[2414.1] {n/a}
Underground Metal--min. 12in. deep; plastic--min. 12in. {18in.} . . . .[2414.9] {1211.6
Plastic requires #18 tracer wire . . . . . . . . . . . . . . .[2414.14.3] {1211.19}
Ferrous pipe must be protected . . . . . . . . . . . . . . . . . .[2414.8] {1211.6}
Exposed underfloor piping min. 6in. above ground . . . . . . .[n/a] {1211.4}
Underslab only if run through gas-tight conduit [2414.11] {1211.4}
Buried plastic must connect to metal =>30in. before vertical [n/a] {1211.6}
Electrically isolate buried ferrous gas pipes . . . . . . . . . . .[2410] {1211.7}
Connections Shutoff valve ahead of union <=6ft. {3ft.} of appliance . . .[2419.5] {1211.18}
Unions adjacent to accessible equipment only . . . . . . . . . .[n/a] {1211.13}
Drip leg if water vapor in gas . . . . . . . . . . . . . . . . . . . .[2418.2] {1211.5}
Flex connection sizing . . . . . . . . . . . . . . . . . . .T-p12 [2421.1.2] {1212.0}
Fireplace with Gas Appliance (see p.23) Req'd valve <=6ft. {4ft.} of fireplace same room. . . . . . . .[2419.5] {1211.17}
Listed caulk around gas pipe penetration. . . . . . . . . . . .[2431.1] {901.3}
Log Lighters installed per manu. instructions. . . . . . . . .[2432.1] {3102.5.1}
Propane (L.P. Gas) Appliance not located where gas may pool . . . . . . . . . . . . [n/a] {1213.5}
Bldg. openings below relief valves min. 5ft. horiz . . . . . . . .[n/a] {1213.9}
Individual Appliance Shutoff Valves
Shutoff valve ahead of union <=6ft. {3ft.} of appliance . . .[2419.5] {1211.18}
May be inside wall furnace access panel . . . . . . . . . . . . . .[n/a] {1211.18}
Final
Gas Appliance Connector Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .T-p12 [2421.1.2] {1212.0}
Max. length 3ft. (6ft. range or dryer) . . . . . . . . . . . . .[2421.1.2] {1212.0X1}
Not pass-through building or appliance wall . . . . . . . .[2421.1.2] {1212.0X2}
Valve immediately ahead of & sized to connector . . . .[2421.1.2] {1212.0X3}
Aluminum alloy for dry interiors only . . . . . . . . . . . . . . .[2421.1] {1212.0X5}
Gas hose {<15ft.} outdoor portable appliance only . . .[2421.1.3] {1212.0X7}
Heat Exchanger Using Potable Water Water separated by two separate walls single wall
if potable side pressure 10psi> than transfer fluid . . .[2902.4.2] {603.4.4}
Backflow preventer (reduced pressure) req'd on solar if chemicals used .2902.4.5] {603.0}
Bathroom Ballcock critical level min. 1in.
above overflow pipe . . . . . . . . . . . . . . . . . . . .F-p14 [2902.3.1] {603.4.2}
Toilet & plumbing fixtures sealed at walls and floors . . .[2705.1] {408.2}
1.6gal. flush water closets (new const. only) . . . . . . . . . . .[local] {local}
Access to tub waste and overflow if slip joints used . . .[2704.1] {405.2}
Books based on 2006 IRC, UMC, & UPC; 2005 & 2008 NEC; 2007 CBC, CPC, CMC & CEC with references to changes from prior editions. Books are published by The Taunton Press Inc. Code Check Copyright 2009 • Code Check is a registered trademark of the Taunton Press, Inc., registered in the U.S. Patent & Trademark Office