Code Check Training Centers
MECHANICAL Water Heater Forced Air Ducts
19-20
Key to Code Check
Building Code Reference!

Water Heater

General IRC UPC
Unions req'd within 12in. . . . . . . . . . . . . . . . . . . . .[2801.3] {609.5}
Full-bore water valve only . . . . . . . . . .F-p12, F-p13 [2903.9.2] {605.2}
Hot and cold pipe insulated within 5ft. . . . . . . . . . . . . .[n/a] {energy}
Insulate hot water recirculating pipes . . . . . . . . . . . .[energy] {energy}
Min. R12 integral (no blanket) . . . . . . . . . . . . . . . . .[energy] {energy}
Electric req's in-sight or lockable disconnect . . . . . .[T4001.5] {NEC422-31b}

Flue (also see termination clearances--page 22)
Draft hood or barometric damper in appliance space [1802.1] {521}
Min. height 5ft. above draft hood . . . . . .[1804.2.3,2426.6.6] {517.2}
Only one draft hood . . . . . . . . . . . . . . . . . .[1801.1,2425.5] {501.0}
No single-wall in cold space . . . . . . . . . . . . . . . . .[2426.7.6] {514.3}

Access & Working Space
Working space by firebox 30in.x30in. min. . . . . . . . .[1305.1] {511.5}
Must be able to remove water heater . . . . . . . . . . .[1305.1] {511.0}
Min. door size 24in.x30in. high OR . . . . . . . . . . . .[1305.1.2] {511.1}
Trap door 22in.x30in. {30in.x30in.} OR . . . . . . . .[1305.1.3,4] {511.3}
Passageway min. 24in. wide,solid floor, max. 20ft. long
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [1305.1.3,4] {511.3,4,5}

Location
Prohibited in bedroom, bathroom, clothes closet or area open to same
except direct-vent or electric appliance . . . . . . . . . . .[2005.2] {509.0}
Over framing req's watertight pan w/1in. {win.} drain [2801.5] {510.7}
In garage--burner/heating element must be 18in. above floor .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F-m1 [2801.6] {510.1}
In garage--protected from vehicle damage . . .F-m1 [1307.3.1] {510.3}
On grade--3in. pedestal req'd. . . . . . . . . .F-m1 [1305.1.4.1] {510.6}
SDC D1 & D2 {zones 3 & 4}--strap upper & lower 3 with min. 4in. clearance to controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-m1 [1307.2] {510.5}

Temperature & Pressure Relief
Temperature-pressure relief required . . . . . . . . . . . .[2803.1] {506.2,608.3}
Drain ends outside <=6in. {6-24in.} from ground . . .[2803.6.1] {608.5}
win. min., no trap, no reduction, no thread on end [2803.6.1] {608.5}
Drain line may not run uphill . . . . . . . . . . . . . . . .[2803.6.1] {608.5}
Watts 210 also req's. pressure relief valve
.......................................................F-m11, F-m12 [2803.1] {Ø, check local}

Why Water Heaters Can Be Very Dangerous

  • Water can scald on contact at temperatures as low as 110°F
  • Water changing state from liquid to steam expands over 1,600 times
  • Water at sea level atmospheric pressure boils at 212°F
  • Temperature relief valves are set at a maximum of 210°F
  • Pressure relief valves are set at a maximum of 150psi
  • Under pressure, the boiling temperature of water goes up
  • At 150psi, water boils at 358°F

The thermostat in a water heater shuts off gas when the temperature needs have
been satisfied. If the thermostat fails, the water heater could have a continuous
rise in temperature and pressure (from expansion of the water). The temperature
and pressure would continue to rise until the pressure exceeds the pressure
capacity of the tank (300psi). In the instant the tank bursts, the superheated
water boils and expands with explosive force. The superheated water turning
to steam turns the water heater into an unguided missile.
To prevent these catastrophic failures, water heaters are required to be protected
for both excess temperature and pressure. Usually, the means of protection is
a combination temperature and pressure (T&P) relief valve.

Water Heater

Watts 210 Valve

Building Code Reference!

Site/Underground

Approved plans & building card on site . . . . . . . . . . .[105.7] {114.2}
Equipment listed and installation instructions on site [1401.1] {302.1}
Energy conservation report . . . . . . . . . . . . . . . . . . .[1101.2] {energy}

Building Code Reference!

Forced-Air Furnace

IRC UMC
Not open to bedroom or bathroom, EXC. . . .[1701.4, 2406.2] {304.5}
Direct vent or elec. furnace OK bedroom or bath . . .[2406.2X] {304.5X}
OK to access attic or crawl equip. through bedroom closet
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [2406.2] {304.5X2}
OK in br. closet if tight door w/closer & outside combust air
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [2406.2X5] {304.5X5}
Furnace room-passageway min. 24in. wide . . .F-m4 [1305.1.2] {307.2}
Work space 30in. deep to height of unit or min. 30in. [1305.1] {307.2}
Total space must be 12in. wider than furnace (exc--replacement furnace)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-m4 [1305.1.1] {304.7}
Combustion chamber--6in. min. to closed door . . .[1305.1.1] {304.7}
Return >10ft.min. from combustion . .F-m4 [1602.3X2,2440.5-4X] {404.1.X3.3}
Receptacle req'd within 25ft. . . . . . . . . . . . . . . . .[3801.11] {306.3}

Underfloor
On slab {min. 3in.} above grade . . . . . . . . . . .[1305.1.4.1] {304.8}
Suspended furnace min. 6in. above grade . . . . . . .[1305.1.4] {304.8}
Passageway--22in. {30in.} x 30in. or manu. spec. .[1305.1.4] {307.4}
Access door max. distance 20ft. to equip. . . . . . . .[1305.1.4] {307.4}
Switch at entrance for light at appliance . . . . . . .[1305.1.4.3] {306.4}

Attic
Access--22in. x 30in. (or dimension of appliance) [1305.1.3] {307.3}
Max. distance from opening 20ft. . . . . . . . . . . . . .[1305.1.3] {307.3}
Solid floor from access door min. 24min. wide . . . .[1305.1.3] {307.3}
Min. 30in. deep platform in front of firebox . . . . . .[1305.1.3] {307.3}
Upright furnace req's 5ft. headroom . . . . . . . . . . . . . . .[n/a] {307.1}
Lighting outlet switched at access door near furnace .. . .[1305.1.3.1] {306.4}

Garage
Any flame or sparking devices min. 18in. above floor
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [1307.3, 2408.2] {308.1.3}
Duct through fire-resistive wall must be 26ga. . . . . .[309.1.1] {603.1.1}
No duct openings into garage . . . . . . . . . . . . . . . .[309.1.1] {n/a}
Protection from impact . . . . . . . . . . . . . . . . . . . .[1307.3.1] {304.9}

Condensing Furnace (High Efficiency)
Condensate drain required . . . . . . . . . . . . . . . . . . .[2426.9] {309.2}
Not drain to public way . . . . . . . . . . . . . . . . . . . . .[2426.8] {309.2}
Drain pipe min. win. with 8in./ft. slope . . . . . . . . . . . .[n/a] {309.2}
May drain to indirect receptor (lav. tailpiece, tub overflow) [n/a] {309.2}

Forced Air Furnace clearances in a closet or closed space

Building Code Reference!

Ducts

General IRC UMC
2 story max. vert. riser on factory-made duct . . . . . .[1601.2] {603.2.1}
Fireblock between floors . . . . . . . . . . . . . .[602.8,1601.3.3] {n/a}
Firestop damper between occupancies as per manuf. [321.3] {605.2}
No duct openings into garage . . . . . . . . . . . . . . . .[309.1.1] {UBC302.4X}
Min. 26ga. sheet steel in attached garage . . . . . . . .[309.1.1] {603.1.1}

Return Air
Sufficient area volume = 25% open to area served OR [1602.3] {404.1.4}
{Hallway must have three doors to area served} . . . . . . .[n/a] {404.1.4X}
Not from bathroom, kitchen, closet or garage . . . . . .[1602.3] {404.1.7}
Source >10ft. from combustion chamber or fireplace
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-m5 [1602.3X3] {404.1X}
Duct min. size 2sq.in./kBtu output rating . . . . .T-m1 [2440.2] {603.5.2}
Installation
Duct to ground min. 4in. clearance . . . . . . . . . . . .[1601.3.6] {603.2.2}
Duct in or under concrete--min. encasement 2in. [1601.1.2] {603.1}
Joints must be airtight . . . . . . . . . . . . . . . . . . . .[1601.3.1] {601.6}
Manufactured ducts taped with UL-181 tape . . . . .[1601.3.1] {601.5}
Flex duct support 12in. strap every 4ft. or manuf. .[1601.3.2] {603.4}
Flex duct flame spreadmax. 25, smoke rating max. 50 . . . .[1601.2.1] {604.3}
Metal duct min. support every 10ft. . . . . . . . . . . .[1601.3.2] {T6-E}

Insulation
R5 inside building, R8 outside . . . . . . . . . . . . . . . .[1103.3] {n/a}
Insulate boots & connectors (1in. fiberglass ~ R2) . .[1103.3] {t6-D}
{Heat zone I, II (temperate except CA) R2.1} . . . . . . . . . [n/a] {t6-D}
{Heat zone III (cold & CA) R4.2} . . . . . . . . . . . . . . . . . .[n/a] t6-D}

Seperation between combustion air and return air

return air sizing



Google
Search codecheck.comSearch WWW